EtherCAT Box 2017 by Beckhoff Automation

More catalogs by Beckhoff Automation | EtherCAT Box 2017 | 100 pages | 2017-09-16

Ads

Contacts for Beckhoff Automation

Beckhoff Automation GmbH
Eiserstraße 5
33415 Verl
Germany

Telefon: + 49 (0) 52 46 / 9 63 - 0
Fax: + 49 (0) 52 46 / 9 63 - 1 98
info@beckhoff.de
http://www.beckhoff.com/

EtherCAT Box 2017 is listed under these categories

Industrial Supply > Industrial Automation

Featured catalog pages of EtherCAT Box 2017

ethercat box digital i/o combi 24 v dc 8 x m8 16 x m8 4 x m12 8 x m12 8-channel ep2308-0001 484 ep2308-0002 485 4 inputs 4 outputs er2308-0001 484 er2308-0002 485 8-channel ep2318-0001 484 ep2318-0002 485 4 inputs 4 outputs er2318-0001 484 er2318-0002 485 8-channel ep2328-0001 487 ep2328-0002 487 4 inputs 4 outputs er2328-0001 487 er2328-0002 487 other filter 3.0 ms imax 0.5 a ethercat box filter 10 µs imax 0.5 a filter 3.0 ms imax 2 a 453 8-channel ep2338-0001 486 ep2338-0002 487 8 inputs/outputs er2338-0001 486 er2338-0002 487 8-channel ep2338-1001 486 ep2338-1002 487 8 inputs/outputs er2338-1001 486 er2338-1002 487 filter 10 µs imax 0.5 a filter 3.0 ms imax 0.5 a 16-channel ep2339-0021 488 16 inputs/outputs ep2339-0022 488 eq2339-0022 546 filter 3.0 ms imax 0.5 a ∑ 4 a er2339-0021 488 er2339-0022 488 16-channel ep2349-0021 489 ep2349-0022 489 16 inputs/outputs er2349-0021 489 er2349-0022 489 filter 10 µs imax 0.5 a ∑ 4 a 16-channel ep2316-0008 485

eqxxxx housing types ethercat box ethercat box stainless steel housing 463 160 43 39 160 72 technical data 4 x m12 dimensions w xhxd 39 mm x 160 mm x 43 mm 72 mm x 160 mm x 43 mm weight depending on device typ 340 g depending on device typ 480 g material stainless steel installation 2 fixing lugs for m5 operating/storage temperature -25…+60 °c 40…+85 °c vibration resistance conforms to en 60068-2-6 shock resistance conforms to en 60068-2-27 emc immunity/emission conforms to en 61000-6-2/en 61000-6-4 protect class/installation pos ip 69k according to en 60529 variable bus interface 2 x m8 socket shielded screw type power infeed/feed through imax 4 a we reserve the right to make technical changes 8 x

ep1816 digital input digital input 24 v dc positive switching d-sub 16-channel digital input 24 v dc 16-channel digital input 24 v dc d-sub type 1/3 positive switching d-sub type 1/3 positive switching industrial housing ep1816-0008 ep1816-3008 connection technology d-sub socket 25-pin d-sub socket 25-pin specification en 61131-2 type 1/3 en 61131-2 type 1/3 input filter 10 µs 10 µs number of inputs 16 16 1 +60 °c +60 °c -25 °c -25 °c 14 1 14 connector assignment see documentation 13 25 13 25 z x y the ep1816 ethercat box with digital inputs acquires the binary control signals from the process level and transmits them in an electrically isolated form to the controller the signals are connected via 25-pin d-sub socket the sensors are supplied from the box supply voltage us the auxiliary voltage up is not used in the input module but may be connected in order to be relayed downstream the ep1816-3008 ethercat box with 16 digital inputs acquires the binary control

digital output ep2816 digital output 24 v dc positive switching 16-channel digital output 16-channel digital output 24 v dc m16 imax 0.5 a ∑ 4 a 24 v dc d-sub imax 0.5 a ∑ 4 a ep2816-0004 ep2816-0008 connection technology m16 19-pin d-sub socket 25-pin load type ohmic inductive lamp load ohmic inductive lamp load max output current 0.5 a each channel individually short-circuit-proof 0.5 a each channel individually short-circuit-proof total current max 4 a total current max 4 a 16 16 industrial housing zinc die-cast housing +60 °c +60 °c -25 °c -25 °c ethercat box number of outputs 1 14 13 25 482 the ep2816-0004 ethercat box with digital outputs connects the binary control signals from the controller on to the actuators at the process level the 16 outputs handle load currents of up to 0.5 a each although the total current is limited to 4 a an output short-circuit is recognised and passed on to the controller the signal connection is realised by a 19-pin m16

analog input ep3204 er3204 analog input rtd the ep3204/er3204 analog input module is intended for the direct connection of resistance thermometers the resistance is measured with a low measuring current linearised and represented in 0.1 °c the ethercat box supports 2 3 and 4-wire measurement on all four channels the measurements serve to eliminate or deduct the parasitic resistance of the sensor cable all inputs are separately configurable for a wide range of sensors for the three measurement procedures and for the direct measurement of resistance 4-channel analog input pt100 rtd parameterisable 16 bit industrial housing ep3204-0002 zinc die-cast housing er3204-0002 connection technology m12 screw type signal type pt100 resolution 0.1 °c per digit conversion time 800 ms up to 2 ms see documentation default approx 85 ms number of inputs 4 +60 °c ethercat box -25 °c 2 492 υ υ υ 1 3 5 4 the ep3204/er3204 with analog inputs allows resistance sensors to be

ep6224 ep6228 communication 4-channel input/output 4-channel input/output 8-channel input/output io-link master module io-link master module io-link master module class a class b class a industrial housing ep6224-2022 ep6224-3022 ep6228-0022 connection technology m12 screw type m12 screw type m12 screw type data transfer rates 4.8 kbaud 38.4 kbaud 4.8 kbaud 38.4 kbaud 4.8 kbaud 38.4 kbaud and 230.4 kbaud and 230.4 kbaud and 230.4 kbaud 4 4 8 io-link interfaces 2 1 3 5 4 ep6224-2022 1 24 v dc 2 n c 3 gnd 4 c/qx 5 n c 2 ep6224-3022 1 24 v dc us 2 24 v dc up 3 gnds 4 c/qx 5 gndp the ep6224 io-link module enables connection of up to four io-link devices e.g actuators sensors or combinations of both a point-to-point connection is used between the terminal and the device the terminal is parameterised via the ethercat master io-link is designed as an intelligent link between the fieldbus level and the sensor wherein parameterisation information can be exchanged bidirectionally via

8 x m8 4 x m12 16 x m8 8 x m12 126 x 30 x 26.5 mm 126 x 60 x 26.5 mm ethercat p combines communication and power in a single 4-wire standard ethernet cable the 24 v dc supply of the ethercat p slaves and of the connected sensors and actuators is integrated us system and sensor supply and up peripheral voltage for actuators are electrically isolated from each other and can each supply a current of up to 3 a to the connected components the eppxxxx ethercat p modules in protection class ip 67 cover the typical range of requirements for i/o signals digital inputs 3.0 ms or 10 µs filter digital outputs with 0.5 a output current combination modules with digital inputs and outputs analog inputs and outputs with 16-bit resolution thermocouple and rtd inputs the epp13xx ethercat p junctions are available for flexible topology configuration the current carrying capacity of 3 a per ethercat p segment already enables a wide range of sensors/actuators to be used if a power supply boost is

epp2008 epp2809 digital output 8-channel digital output 16-channel digital output 16-channel digital output 24 v dc m12 imax 0.5 a ∑ 3 a 24 v dc m8 imax 0.5 a ∑ 3 a 24 v dc m12 imax 0.5 a ∑ 3 a epp2008-0022 epp2809-0021 epp2809-0022 m12 screw type m8 screw type m12 screw type ohmic inductive lamp load ohmic inductive lamp load ohmic inductive lamp load 0.5 a per channel individually short-circuit-proof 0.5 a per channel individually short-circuit-proof 0.5 a per channel individually short-circuit-proof total current max 3 a total current max 3 a total current max 3 a 8 16 16 +60 °c +60 °c -25 °c -25 °c -25 °c ethercat box +60 °c b 2 3 3 1 a 5 4 4 4 1 3 a 2 b 1 1 a a 3-wire 2-wire 3-wire 2-wire 3-wire 2-wire 24 v dc 15 20 24 v dc 15 20 24 v dc 15 20 typ 100 ma typ 100 ma typ 100 ma – – – max 1.5 a max 1.5 a max 1.5 a typ 20 ma load typ 20 ma load typ 20 ma load 500 v 500 v 500 v 1 output per m12 plug –

analog input epp3174 epp3184 ethercat box analog input -10…+10 v 0/4…20 ma rtd 530 the epp3174 and epp3184 ethercat p box modules evaluate analog standard signals within the range of -10/0 v to +10 v or 0/4 ma to 20 ma with 16-bit resolution the signal form is separately configurable for each channel the epp3174 evaluates the difference between the two input signals input and input these must be referred to the ground potential of the load voltage up the dc component does not affect the measurement as long as it is in the common mode range the measurement in the epp3184 is single-ended and the negative reference potential is fixed to the ground potential of the supply voltage up the epp3204 analog input module is intended for the direct connection of resistance thermometers the resistance is measured with a low measuring current linearised and represented in 0.1 °c the ethercat p box supports 2 3 and 4-wire measurement on all four channels the measurements serve to

system epp13xx system junctions ethercat p junction ethercat p junction with feed-in with refresh ethercat p junction technical data epp1322-0001 epp1332-0001 epp1342-0001 task within coupling to the ethercat network 3-port ethercat p junction and 3-port ethercat p junction ethercat system ethercat p junction and refresh of us and up feed-in of us and up data transfer rates 100 mbaud 100 mbaud 100 mbaud protocol ethercat/ethercat p ethercat p ethercat p ethercat box +60 °c 4 2 4 2 3 1 3 1 +60 °c -25 °c 4 2 4 2 3 1 3 1 +60 °c -25 °c 4 2 4 2 3 1 3 1 4 2 4 2 4 2 3 1 3 1 3 1 4 2 4 2 4 2 3 1 3 1 3 1 -25 °c 540 2 4 4 2 2 4 1 3 3 1 1 3 3 in out 4 in 2 1 out nominal voltage 24 v dc 15 20 24 v dc 15 20 24 v dc 15 20 distributed clocks – – – number of channels in 1 x ethercat out 3 x ethercat p in 1 x ethercat p out 3 x ethercat p in 1 x ethercat p out 3 x ethercat p bus interface m8 socket shielded screw type m8 socket shielded screw type m8

4-channel analog input 4-channel analog input pt100 rtd parameterisable thermocouple/mv parameterisable 16 bit 16 bit eq3204-0002 eq3314-0002 m12 screw type m12 screw type pt100 thermocouple 0.1 °c per digit 0.1 °c per digit analog input 800 ms up to 2 ms see documentation default approx 85 ms 2.5 s up to 20 ms see documentation default approx 250 ms 4 4 p p p 2 3 1 4 +60 °c +60 °c -25 °c -25 °c i 2 3 1 5 4 5 the eq3204 ethercat box with analog inputs allows resistance sensors to be connected directly the module’s circuitry can operate the sensors using 2 3 or 4-wire connection techniques linearisation over the full temperature range is realised with the aid of a microprocessor the temperature range can be selected freely the module can also be used for simple resistance measurement the module’s standard settings are resolution 0.1°c in the temperature range of pt100 sensors in 2-wire connection the eq3314 ethercat box with analog inputs permits