product introduction improved productivity suitable rapid acceleration/deceleration operation is available the standard power regenerative braking function provides suitable rapid acceleration/deceleration operation with quick speed response when a power failure for 2 s or shorter occurs torque output is reduced to zero without tripping and then returns after the power recovery automatic restart can be performed after the operation stops due to a power failure for 2 seconds or longer automatic re-acceleration can be performed for the motors during deceleration by coasting or being stopped

product introduction energy saving 100 mve2 energy recovered speed 80 60 40 20 0 time regenerative braking of a conveyor application allows saving of energy during each conveyor stop regenerative operation of downhill conveyors allows long term energy savings high efficiency the tmdrive-mve2 has low switching losses of the main circuit elements low input side harmonic currents not only result in low losses but also contributes to improvement of the efficiency of the equipment as a whole by eliminating harmonic filters or power factor improving capacitors 1 tmdrive-mve2 variable speed drive system has conversion efficiency of approximately 97 pump boiler and conveyor applications 1 at rated speed and full load regenerative power feedback to the power supply in variable torque load applications such as fans pumps or blowers variable speed operation of inverters achieves significant energy saving effect as compared to the constant speed operation using a commercial power supply 50 hz

product introduction power supply friendly input harmonic suppression

product introduction simple commissioning operation and troubleshooting an lc display is used on the operation panel the inverter operating condition can be monitored on the easy-to-view display screen parameter setting and troubleshooting can be also performed easily

circuit configuration standard connection diagram

standard specifications standard rating item specification at 3.3 kv output kva 200 300 6.6/6.0 kv 4.16 kv 3.3/3.0 kv cell frame frame 600 100 800 950 200 overload 60 seconds 1100 1300 300 1500 400 110 rated current a 35 53 70 105 140 166 192 227 263 applicable motor output kw 1 160 250 320 450 650 750 900 1000 1250 at 4.16 kv output kva 500 1000 1380 1890 cell frame frame 100 200 300 400 1400 1600 1900 overload 60 seconds 110 rated current a 69 138 191 262 applicable motor output kw 1 400 810 1120 1600 at 6.6 kv output kva 400 600 800 1000 cell frame frame 1200 100 200 overload 60 seconds 2200 3000 400 110 35 53 70 87 105 122 140 166 192 227 262 applicable motor output kw 1 315 450 650 810 1000 1130 1250 1600 1800 2250 2500 at 11 kv output kva 660 990 1320 2000 2640 3080 3630 4290 100 200 overload 60 seconds 300 5000 400 110 rated current a 35 53 70 105 139 162 191 226 263 applicable motor output kw 1 500 800 1000 1600 2040 2500 2800 3500 3860 1 approximate value for the standard

standard specifications protective functions item abbreviation content related parameter cell converter over current xn_c_oca1 the ac over current detection circuit hardware of the x-phase n th cell converter activated cell over voltage p side xn_ovp1 the p side over voltage detection of the x-phase n th cell activated cell over voltage n side xn_ovn1 the n side over voltage detection of the x-phase n th cell activated cell over heat xn_oh1 an overheat condition of the x-phase n th cell is detected cell gate power supply failure xn_gpsf1 the gate power supply failure detection circuit hardware of the x-phase n th cell activated cell serial communication link failure xn_link_f1 serial communication link failure of the x-phase n th cell was detected cell fuse blown xn_fuse1 the fuse blown detection circuit hardware of the x-phase n th cell activated cell failure xn_cell_f1 an x-phase n th cell failure has occurred ac overcurrent oca the ac over current detection circuit hardware

standard specifications protective functions item abbreviation content related parameter 16 equipment ventilating redundancy fan stopped timer c_fn_b a redundant equipment ventilating fan error has been detected this detection is made by an auxiliary contact of the fan mccb ground detection timer gr_t a ground fault has been detected cp_gdv time_gr flt_gdv ground detection alarm gr_a gr_a detects when the ground current increases above the ground detection alarm level cp_gdv_a flt_gdv dc voltage drop uvd a power supply voltage drop was detected in the dc main circuit while the drive was running dc voltage drop starting interlock uv_sil system configuration error sys_err set parameter check error para_err this is a checksum error of parameter setting value external interlock il an external interlock signal has been lost external equipment electrical condition ready condition uva_ex uva_ex is an external electrical condition signal external safety switch uvs panel interlock switch on

standard specifications option item abbreviation output frequency maximum output frequency for 3 kv/4 kv/6 kv 120 hz for 11 kv 72 hz vector control with sensor encoder control method automatic restart control after power failure between 2 seconds and 6 seconds synchronous transfer to and from commercial power supply shock-less switching over between power supplies personal computer application software for maintenance and adjustment os windows®7 professional 32-bit version maintenance tools multi-language display on the operation panel supports nine languages sm control soft start separate step-down transformer for the control power supply from 400 v to 200 v duplex cooling fan others specified painting color outlet control panel illumination light space heater separate input transformer excitation inrush current limit circuit small-capacity for installing the transformer separately or using the excitation inrush current limit circuit contact your sales representative for the

outline dimensions 6.6 kv–400/600/800 kva 6.6 kv–1000/1200/1400/1600 kva left side view left side view front view 50 50 2050 2050 400 400 front view 970 30 1600 1000 30 970 600 1800 1000 600 3400 1000 3200 approx mass 4700 kg approx mass 3400 kg unit mm 6.6 kv–1900/2200/2600/3000 kva left side view 1070 30 650 2050 1500 50 100 2050 490 front view 600 4800 1100 approx mass <1900/2200 kva 6750 kg <2600/3000 kva 7150 kg unit mm 11 kv–660/990/1320/2000/2640 kva left side view 2300 30 700 2500 1700 1200 600 100 1170 2400 400 front view 5500 approx mass <660/990/1320kva 7800 kg unit mm <2000/2640kva 8000 kg 11 kv–3080/3630/4290/5000 kva left side view right side view 1500 30 490 2300 2900 2800 600 2400 2500 700 100 1470 100 2600 400 front view 30 1270 19 1300 7000 approx mass <3080/3630kva 13350 kg <4290/5000kva 13500 kg unit

global partner local friend european offices representatives germany russia geva wiener straße 89 a-2500 baden phone +43 02252 85 55 20 austria czech republic autocont c.s s.r.o kafkova 1853/3 cz-702 00 ostrava 2 phone +420 595 691 150 czech rep mitsubishi electric europe b.v radlická 751/113e avenir business park cz-158 00 praha 5 phone +420 251 551 470 spain mitsubishi electric europe b.v carretera de rubí 76-80 apdo 420 e-08190 sant cugat del vallés barcelona phone +34 0 93 5653131 ooo technikon prospect nezavisimosti 177-9 by-220125 minsk phone +375 017 393 1177 belarus hans fØlsgaard a/s theilgaards torv 1 dk-4600 køge phone +45 4320 8600 mitsubishi electric europe b.v 25 boulevard des bouvets f-92741 nanterre cedex phone +33 01 55 68 55 68 france mitsubishi electric europe b.v scandinavia sweden fjelievägen 8 se-22736 lund phone +46 0 8 625 10 00 esco drives culliganlaan 3 be-1831 diegem phone +32 02 717 64 60 belgium provendor oy teljänkatu 8 a3