Page 132 of Wood Construction Connectors 2006 Catalog by Simpson Strong-Tie
133
Plated Truss Connectors
LTHJ Truss Hip/Jack Hangers
Single piece, non-welded truss hip/jack connector.
MATERIAL: 18 gauge.
FINISH: Galvanized; also available in Z-MAX
coating. See Corrosion Resistance, page 6-7.
INSTALLATION: Use all specified fasteners. See General Notes.
All multiple members must be fastened together to act
as a single unit.
The two 10d common nails into the jack must be driven
at an angle through the side plate slot and jack, and into
the carrying member; see HUS for double shear nailing
details. The end of the jack cannot be more than "
from the back plate to meet required nail penetration.
Should be attached to a double girder truss to allow
for code-required minimum nail penetration.
Distribute 75% of the total load to the hip member.
With single 2x carrying members, use 10dx1 nails
and use 0.82 of the table value.
TO ORDER: Specify LTHJL for left 45 skewed hip truss and
LTHJR for right 45 skewed hip truss.
OPTIONS: SLOPE AND/OR SKEW
Available in hip slopes up to 45 and/or skews left or
right from 46 to 67 .
For optional configurations, loads are 100% of table
loads.
To order, specify degree of slope and/or skew left or right.
Example: To order an LTHJ sloped down 45 and
skewed right 55 , order an LTHJXD45 R55.
CODES: See page 12 for Code Listing Key Chart.
Model
No.
Fasteners
Carried
Member
Doug Fir-Larch/Southern Pine Allowable Loads
Spruce-Pine-Fir Allowable Loads
Carrying
Member
Hip
Jack
Uplift 1
(133)
Uplift 1
(160)
Floor
(100)
Snow
(115)
Roof
(125)
Wind
(133)
Uplift 1
(133)
Uplift 1
(160)
Floor
(100)
Snow
(115)
Roof
(125)
Wind
(133)
LTHJR/L
12-10d
4-10dx1
2-10dx1
and
2-10d
Hip
485
580
1135
1310
1420
1425
415
500
980
1130
1225
1225
6, 121
Jack
250
250
380
435
475
475
215
215
330
380
410
410
Total
735
830
1515
1745
1895
1900
630
715
1310
1510
1635
1635
Code
Ref.
1. Uplift loads include a 33% and 60% increase for earthquake or wind loading
with no further increase allowed; reduce where other loads govern.
2. Allowable loads for 10d commons also apply when 16d sinkers are used.
3. Combine hip and jack loads for total capacity.
4. Wind (133) is a download rating.
5. Truss chord cross-grain tension may limit allowable loads. Refer to Technical
Bulletins T-ANSITPISPF, T-ANSITPISP and T-ANSITPIDF for allowable loads that
consider ANSI/TPI 1-2002 wood member design criteria.
6. NAILS: 10d 0.148" dia. x 3" long, 10dx1 0.148" dia. x 1 long.
See page 16-17 for other nail sizes and information.
LTHJL Plan View
(LTHJR similar)
LTHJR
Hip Skewed 45 Right
(LTHJL similar)
LTHJX
Skewed Right
Typical LTHJL Installation
Available with additional corrosion protection. Check with factory.