Page 147 of Wood Construction Connectors 2006 Catalog by Simpson Strong-Tie
148
Masonry Connectors
HU/HUC/HSUR/L Hangers
Down
(133) (160) (100/115/125)
HU26
4 Titen x 2
2-10dx1
240
290
1545
HU28
6 Titen x 2
4-10dx1
480
575
2400
HU210
8 Titen x 2
4-10dx1
480
575
2400
HU46
12 Titen x 2
6-10d
905
1085
3950
170
HU26-2
12 Titen x 2
6-10d
905
1085
3950
HU48
14 Titen x 2
6-10d
905
1085
4350
HU28-2
14 Titen x 2
6-10d
905
1085
4350
HU410
18 Titen x 2
10-10d
1505
1810
5085
HU210-2
18 Titen x 2
10-10d
1505
1810
5085
HSUL/R26-2 12 Titen x 2
4-16dx2
715
815
2625 6
Allowable Loads
Uplift
Fasteners
CMU
4 Titen x 1
6 Titen x 1
8 Titen x 1
12 Titen x 1
12 Titen x 1
14 Titen x 1
14 Titen x 1
18 Titen x 1
18 Titen x 1
12 Titen x 1
Concrete
Joist
Code
Ref.
Model No.
HUC410 Installed on
Masonry Block End Wall
HUC410 Installed on
Masonry Block Sidewall
HSUR/L26-2 Installed on
Masonry Block Sidewall
HU and HUC products are heavy duty face mount joist hangers made from 14 gauge
galvanized steel.
The HUC is a concealed flange version of the HU. Concealed flange hangers
have the face flanges turned in.
HU is available with A flanges concealed, provided the W dimension is 2 or greater,
at 100% of the table load. Specify HUC.
HU is available with one flange concealed when the W dimension is less than 2 at
100% of the table load.
For allowable loads on HU products not listed in the table request T-HUHUCTTN.
INSTALLATION:
These hangers are attached to grouted CMU walls using x 2 hex head Titen screws
or for concrete walls using x1 Titen screws. Titen screws are not provided.
Drill the diameter hole to the specified embedment depth plus ".
Alternatively, drill the diameter hole to the specified embedment depth and
blow it clean using compressed air.
Caution: Oversized holes in the base material will reduce or eliminate the
mechanical interlock of the threads with the base material and will reduce the
anchors load capacity.
The hangers should be installed such that a minimum end and edge distance of
1 is maintained.
Not recommended for exposed external applications.
CODES: See page 12 for Code Listing Key Chart.
HUC410
1. Uplift loads have been increased 33% and 60% for earthquake or wind duration. No further increase is allowed.
2. Grout strength for concrete masonry installation shall be 2500 psi minimum.
3. Contact Simpson for loads on other models.
4. The HU28 can be ordered skewed 45 and achieve the same loads.
5. See page 147 for Titen screw information.
6. Loads for the HSUL/R shall be 0.8 the table loads for concrete applications.
7. Table allowable loads were determined using test ultimate/3 or nail calculation values.
8. NAILS: 16dx2 0.162" dia. x 2 long, 10d 0.148" dia. x 3" long,
10dx1 0.148" dia. x 1 long. See page 16-17 for other nail sizes and information.