Hanger Options
HANGER OPTIONS
B/BA/LBV/HB/HHB/GB/HGB
Typical LBV Sloped Down
Installation with Full Backing
Top View B Hanger
Skewed Right
Typical LBV Sloped
Down with Top Flange Open
B Hanger Sloped Down and Skewed Left with Sloped Top Flange Installation
When ordering, specify Low Side Flush, Center Flush or High Side Flush
1. Use this table to calculate allowable loads for modified hangers.
2. Examples: LBV with top flange sloped down right 30 , reduce download to
[(90-30)/90] x table load.
B skewed right 25 (download), multiply .95 x table load.
3. For hangers with heights less than Min. Height shown, use the lower of 0.75
(reduction factor) or the reduction factor shown in the table.
4. For sloped-only, minimum height is 9 ".
5. Reduction factors shown in this table apply to the Nailer Table on page 100.
6. For heights 22" and less, use 1.00.
Typical LBV Sloped
Down on Nailer
Typical BD
Saddle Installation
Model No.
Sloped
Only
TF Down
LBV
Angle Limit
Download
Uplift
Angle Limit
Download
Uplift
Angle Limit
Download
Uplift
B
HHB,
GB,
HGB
TF Open/Closed
45
1.00
0.70
Skewed
Only
Sloped
Skewed
Backed
Sloped Only 4 or Sloped Skewed
Non-Backed
Min. Height 3
Min. Height 3
Min. Height 3
9
-
-
-
-
-
-
-
-
1.00
45
No Uplift
45
45
No Uplift
No Uplift
1.00
1.00
1.00
45
14
14
14
14
14
14
No Uplift
45
45
No Uplift
No Uplift
1.00
0.85
Angle Limit
Download
Uplift
HB
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Min. Height 3
(90-x) 90
35
1.00
35
1.00
(90-x) 90
(90-x) 90
30
1.00
30
1.00
(90-x) 90
1.00
45
1.00
45
1.00
0.90
1.00
45
1.00
45
1.00
0.95
1.00
45
0.90 6
45
0.90 6
0.90
9
9
9
9
14
9
9
9
14
14
35
1.00
(90-x) 90
30
1.00
(90-x) 90
45
1.00
0.90
45
0.80
0.95
45
0.80
0.90
9
9
9
14
14
Hanger Modification Reduction Factors
Nailers 5
SADDLE HANGER
Saddle hangers are made to order; add D to model
(e.g. BD412); specify S (for saddle) dimension.
They may be used for most conditions except at
end wall locations and are preferred for nailer
applications. Minimum S dimension (saddle width)
is 3 ". Minimum member width is 3 ". Minimum
nailer thickness apply (see page 77). Saddle hangers
achieve catalog load listed. Saddle hangers on stud
walls do not achieve catalog loads.
MATERIAL:
Gauge may vary from that specified depending
on the manufacturing process used. Hanger
configurations, height and fastener schedules
may vary from the tables depending on the
joist size, skew and slope.
CODES: Modified hangers, due to their numerous
variations, are not in code reports.
LOADS: For multiple modifications on the same
connector, use the smallest reduction factor
that yields the lowest design loads.
INSTALLATION: Fastener quantities will typically increase
beyond the amount specified in the standard
hanger tables.
Web stiffeners are required for I-joists.
Fill all holes with the table-specified
fastener types.
Bevel cut the carried member for skewed
applications.
B hangers for sloped seat installations are
assumed backed. For non-backed nailer
applications see Hanger Modification
Reduction Factors table.