Page 27 of Wood Construction Connectors 2006 Catalog by Simpson Strong-Tie
FINISH: Simpson gray paint
INSTALLATION: Use all specified fasteners. See General Notes.
Bolt holes shall be a minimum of to a maximum of larger
than the bolt diameter (per the 2001 NDS, section 11.1.2.).
Check the rebar spacing requirements on all installations.
OPTIONS: Sawn timber and other sizes may be ordered by specifying
special dimensions; use the letter designations shown on
the illustrations.
Specify if two-bolt GLB model is desired; see illustration.
CODES: See page 12 for Code Listing Key Chart.
Model
No.
Dimensions
Allowable Bearing Loads (lbs) 1,2,8
W 6
PD
PW
PT
Masonry
@ 195 psi
Wood F
c
on Glulam Width
5
3
6
8
10
HGLBA
3 to 9
5
10
2
HGLBB
3 to 9
6
10
2
HGLBC
3 to 9
7
10
2
HGLBD
3 to 9
8
10
2
20, 80,
124
GLBT512
3 to 11
5
12
2
GLBT612
3 to 11
6
12
2
GLBT516
3 to 15
5
16
2
GLBT616
3 to 15
6
16
2
GLBT520
3 to 19
5
20
2
GLBT620
3 to 19
6
20
2
24500
29400
34300
39200
25725
31850
25725
31850
25725
31850
18900
22680
26460
30240
19845
24570
19845
24570
19845
24570
14350
17220
20090
22960
15070
18655
15070
18655
15070
18655
19500
23400
27300
31200
24570
30420
32760
40560
40950
50700
9750
11700
13650
15600
12285
15210
16380
20280
20475
25350
8750
10500
12250
14000
9190
11375
9190
11375
9190
11375
8260
8260
8260
8260
8260
8260
8260
8260
8260
8260
31605
39130
31605
39130
31605
39130
Masonry
@ 390 psi
Code
Ref.
Bolts
Allowable
Horizontal
Bolt
Loads 3,4
(lbs)
1. Allowable masonry bearing loads based on f'm of 1,500 psi. Wood bearing based on 560 psi.
2. When installed on masonry, use the lesser of the masonry or the wood allowable load values. When installed on
concrete, a minimum f'c 2000 psi shall be used and use the wood values as the limiting allowable bearing load values.
3. Allowable horizontal loads are bolt values and include a 33% increase for earthquake or wind loading.
Loads must be reduced if stresses in masonry or concrete are limiting.
4. Beams must fully bear on base plate.
5. The GLBT5 has a WT4x9 structural tee; the GLBT6 has a WT4x12 structural tee.
6. Specify W dimension when ordering.
7. For 2003 International Building Code loads: Masonry 195 psi values are not applicable and
Masonry 390 psi values shall be reduced by 0.96.
GLBT
GLB
HGLB
Typical GLB
Installation
Model
No.
Dimensions
Allowable Bearing Loads (lbs) 1,2
W
PD
PW
PT
Masonry
@ 195 psi
Masonry
@ 390 psi
Wood
Fc
GLB5A
5
5
7
3 ga
1
GLB5B
5
6
7
1
GLB5C
5
7
7
1
GLB5D
5
8
7
1
GLB7A
6
5
9
3 ga
1
GLB7B
6
6
9
1
GLB7C
6
7
9
1
GLB7D
6
8
9
6825
8190
9555
10920
8775
10530
12285
14040
13650
16380
19110
21840
17550
21060
24570
28080
14350
17220
20090
22960
14350
17220
20090
22960
1
20, 80,
124
Code
Ref.
Bolts
1.Allowable masonry bearing loads based on f'm of 1,500 psi.
Wood bearing based on 560 psi.
2.When installed on masonry, use the lesser of the masonry or the wood allowable
load values. When installed on concrete, a minimum f'c 2000 psi shall be used
and use the wood values as the limiting allowable bearing load values.
28