NEW! SSTB14 is a diameter anchor bolt designed and tested
specifically for shallow foundation installations.
Extensive SSTB testing has been done to determine the design load
capacity at a common application, the garage stem wall. Design loads are
based on a series of five tests, with a three-times reduction factor.
SPECIAL FEATURES: Rolled threads for higher tensile capacity.
Offset angle reduces side-bursting, provides more concrete cover.
Stamped embedment line aids installation. Configuration results in minimum rebar interference.
MATERIAL: ASTM A36
FINISH: None. May be ordered HDG; check factory
INSTALLATION: SSTB is used for monolithic and two-pour installations.
Nuts and washers are not supplied with the SSTB; install
standard nuts, couplers and/or washers as required.
REINFORCED CONCRETE FOUNDATION
Install SSTB before the concrete pour using AnchorMates (see page 22).
Install the SSTB per plan view detail shown on page 34. Install one #4
rebar 3" to 5" (may be foundation rebar not post-tension cable) from
the top of the foundation. The SSTB does not need to be tied to the rebar. Minimum concrete compression strength is 2500 psi. Unless noted
otherwise, no special inspection is required for foundation concrete
when the structural design is based on concrete no greater than
2500 psi (UBC Section 1701.5.1 and IBC Section 1704.4).
Unless otherwise noted, do NOT install where: (a) a horizontal cold
joint exists within the embedment depth between the slab and
foundation wall or footing beneath, unless provisions are made to
transfer the load, or the slab is designed to resist the load imposed by
the anchor; or (b) slabs are poured over concrete block foundation walls.
REINFORCED CONCRETE BLOCK
Before concrete pour, install diagonally at approx. 45 in the cell per
plan view detail shown on page 34.
Horizontal #4 rebar (minimum 56" long centered about the anchor
bolt) approximately one rebar 12" from the top and two rebars
approximately 28" from the top. Vertical #4 rebar (minimum 24" long)
install with maximum 24" o.c. spacing.
Grout all cells with minimum 2000 psi concrete. Vibrate the
grout per the 1997 Uniform Building Code, Section 2104.6.2,
2003 International Building Code, Section 2104.1.
CODES: See page 12 for Code Listing Key Chart.
Model 7
No.
Stemwall
Width
Dia.
Length
Min
Embed
le
Allowable Tension Load 1,2
Concrete
8" CMU
Block End
Concrete 12
8" CMU
Block
Concrete 4
fc =
2500 psi
Code
Ref.
SSTB16
6
17 (SSTB16L 19 )
12
4420
SSTB14
9
15
11
3835 11
4780
1850
SSTB20
6
21 (SSTB20L 24 )
16
4600
4780
1850
SSTB24
6
25 (SSTB24L 28 )
20
5175
4780
1850
23, 94
23, 94,
136
160
SSTB28
8
29 (SSTB28L 32 )
24
10100
6385
4815
SSTB34
8
34
28
10100
6385
4815
SSTB36
8
36
28
10100
6385
4815
1. Loads may not be increased for short-term loading. Loads apply to earthquake and wind loading.
2. Minimum anchor center-to-center spacing is 2le for anchors acting in tension at the same time for full load.
3. The SSTB was tested in a stem wall with a minimum amount of concrete cover.
4. Maximum allowable load is 8150 lbs. for SSTB28, 34 and 36 when used 5" from the end of a concrete
foundation. Use full table load when installed 24" from the end or installed in a corner condition (see illustration).
5. Connection is limited by the lowest of bolt or holdown capacity.
6. PHD and HTT minimum end distance is 4 ".
7. Order the SSTBL models for longer thread length (5 ex. SSTB24L. SSTBL and SSTB loads are the same.
Not available on SSTB14.
8. SSTB34 has 4 of thread and SSTB36 has 6 ". These two models are not available in SSTBL versions.
9. Use 90% of the table load for 2000 psi concrete.
10. See page 34 for Additional Anchor Design information.
11. Allowable load for SSTB14 is 5020 lbs. when f'
c
= 3000 psi. See T-SSTB for additional information.
12. Minimum end distance required to achieve table loads is le.
SELECTION GUIDE
(Per Anchor Bolt Diameter)
Model
No.
2x, 3x, 2-2x Sill Plates
Mono Pour
Two Pour
PHD2 1
HD2A
HDU2
LTT20B
LTTI31
HTT16
HDU4
HD5A
SSTB16
SSTB20
SSTB14
SSTB20
PHD5 1
MTT28B
SSTB20
SSTB24
HTT22
HDC5/22
HDC5/4
SSTB24
PHD6 1
HD6A
HD8A
HDU8
HD10A
HDQ8 1
HDC10/22 4
HDC10/4 4
SSTB28
SSTB34
SSTB16
(others similar)
SSTB16L
(others similar)
U.S. Patent
5,317,850
End Wall
(Note 4)
Continuous
Stemwall
Corner Installation
TYPICAL PLAN VIEWS OF REBAR INSTALLATION
See page 34 for additional installation details.
1.SSTBL models are recommended for PHD
and HDQ8 holdowns on 2-2x and 3x sill plates.
2. No cold joint within embedment depth unless
provisions are made to transfer the load.
3.The design engineer may specify an alternate
anchorage system, provided the anchor
diameter is the same.
4.Increase the embedment depth 2 to
accommodate the HDC standoff block.
Available with additional corrosion protection. Check with factory.
Identification
on the bolt
head showing
embedment
angle and model.
33