Catalog: Air-cooled Screw chillers
Company/Brand: Voltas Limited
2 meter loop in Air-cooled Screw chillers by Voltas Limited
in order to select a packaged chiller 1 2 3 4 5 6 7 required cooling capacity in ... temperature °f or °c elevation feet or meters electrical power characteristics ... local with which unit must comply step 2 cooler gpm and pressure drop gpm ... specified tons x 24 100 x 24 240 gpm cooling range 10 referring to page ... 20 for the physical specifications we note ... using curve 4 of 15.6 ft of water at 240 gpm step 3 chilled water pump ... to the pressure drop calculated in step 2 add the pressure drop through the ... chilled water loop piping valves and equipment this will ... the physical data table found on page 20 note that the standard ambient with fan ... cycling is 20°f since requirement is for 0°f the ... following unit minimum circuit ampacity 229 unit maximum fuse size 300 8 9 10 any ...

example 2 s.i units select an air cooled packaged ... chiller for the following conditions 230 kwo at 13°c entering 6.67°c leaving ... ambient is 10°c altitude is 600 meters cooler fouling factor 0.0176 electrical ... with a single connection required brine loop to be 40 ethylene glycol by weight step ... 1 unit selection for 600 meter elevation divide the required tonnage ... altitude correction factor from table 23a 230 232.3 kwo .99 to correct for ... evaporator fouling consult table 23b in this example the fouling factor is 0 ... c1 and make the following adjustment 232.3 238.8 kwo .973 the input power kwi is ... by k1 the kw factor entering the table 24a on page 24 we see that an acdx-b 68 ... water at sea level has a capacity of 240.9 kwo drawing 77.3 compressor kwi the ...